CARTRIDGE & FLAME PROOF TYPE GAS DETECTOR GTD-5000F SERIES |
ǰ (Model) |
GTD-5000F |
(Measuring gas) |
LNG, LPG, , ź, ź O2, CO, CL2, NH3 ü |
(Measuring type) |
|
(Measuring method) |
|
(Measuring range) |
|
ӵ (Response time) |
Flammable gases( < 15sec / 90% scale) VOC gases(< 5sec / 90% scale) Toxic gases( < 45sec / 90% scale) |
Ȯ (Accuracy) |
3% / Full scale |
(Parameter controls) |
׳Ʈ(ڼ) (, ) |
۵ ǥ (Operation mode display) |
Alarm / Trouble LED , Flow rate |
ǥ (Measuring value display) |
FND Display(4-digit) |
ȣ(Output signal) |
: 4-20 mA DC |
|
: 3 mA DC |
|
: 2 mA DC |
|
: 0 mA DC Digital output : RS-485 Modbus(Option) HART Communication (Option) PoE(Power over Ethernet) (Option) |
̺/۰Ÿ (Cable/Distance) |
Power + Signal cable : 3-wire > 1.5sq(AWG16) / 1000m max 4 - 20mA DC Signal : 2000m RS-485 Modbus Signal : 1000m |
(Conduit connection) |
G. Rc. NPT 1/2" & 3/4" (G 3/4" : Standard) |
ġ (Mounting type) |
Wall mount |
۵ µ (Operating temperature) |
-40 ~ +6 |
۵ (Operating humidity) |
5 to 99% RH (Non-condensing |
۵ (Operating power) |
Standard : 18 ~27V DC (24V DC normal) / 500mA max |
ũ (Dimensions) |
226 x 154 x 238mm (W X H X D) |
(Weight) |
Standard type : 5kg |
(Approval) |
Flame proof type (Ex d IIC T6, IP65) KCS |